OpenStudio Results
Model Summary
| Information | Value | Units |
|---|---|---|
| Building Name | NECB 2011-SmallHotel-NECB HDD Method-CAN_PQ_St.Hubert.713710_CWEC.epw created: 2017-06-30 16:46:06 +0000 | building_name |
| Net Site Energy | 2,892,065 | kBtu |
| Total Building Area | 43,202 | ft^2 |
| EUI (Based on Net Site Energy and Total Building Area) | 66.94 | kBtu/ft^2 |
| OpenStudio Standards Building Type | SmallHotel |
| Value | |
|---|---|
| Weather File | St Hubert PQ CAN WYEC2-B-04712 WMO#=713710 |
| Latitude | 45.52 |
| Longitude | -73.4 |
| Elevation | 89 (ft) |
| Time Zone | -5.0 |
| North Axis Angle | 180.00 |
| ASHRAE Climate Zone |
| Maximum Dry Bulb (F) | Daily Temperature Range (R) | Humidity Value | Humidity Type | Wind Speed (mph) | Wind Direction | |
|---|---|---|---|---|---|---|
| ST HUBERT ANN CLG .4% CONDNS DB=>MWB | 86.18 | 18.54 | 71.24 | Wetbulb [F] | 11.86 | 240.0 |
| ST HUBERT ANN CLG .4% CONDNS WB=>MDB | 82.4 | 18.54 | 73.94 | Wetbulb [F] | 11.86 | 240.0 |
| ST HUBERT ANN HTG 99.6% CONDNS DB | -11.74 | 0.0 | -11.74 | Wetbulb [F] | 7.38 | 270.0 |
| Time Setpoint Not Met | Time (hr) |
|---|---|
| During Heating | 55.75 |
| During Cooling | 77.75 |
| During Occupied Heating | 53.0 |
| During Occupied Cooling | 77.75 |
| Tolerance for Time Setpoint Not Met | Temperature (F) |
|---|---|
| Heating | 1.8 |
| Cooling | 1.8 |
Annual Overview
One or more tables in Annual Overview section returned false and was skipped.
| End Use | Consumption (kBtu) |
|---|---|
| Heating | 1,213,756 |
| Cooling | 97,502 |
| Interior Lighting | 372,615 |
| Exterior Lighting | 0 |
| Interior Equipment | 93,379 |
| Exterior Equipment | 0 |
| Fans | 163,811 |
| Pumps | 2,910 |
| Heat Rejection | 199 |
| Humidification | 0 |
| Heat Recovery | 0 |
| Water Systems | 947,893 |
| Refrigeration | 0 |
| Generators | 0 |
| Fuel | Consumption (kBtu) |
|---|---|
| Electricity | 2,892,065 |
| Natural Gas | 0 |
| Additional Fuel | 0 |
| District Cooling | 0 |
| District Heating | 0 |
| End Use | Consumption (kWh) |
|---|---|
| Heating | 355,717 |
| Cooling | 28,575 |
| Interior Lighting | 109,203 |
| Exterior Lighting | 0 |
| Interior Equipment | 27,367 |
| Exterior Equipment | 0 |
| Fans | 48,008 |
| Pumps | 853 |
| Heat Rejection | 58 |
| Humidification | 0 |
| Heat Recovery | 0 |
| Water Systems | 277,800 |
| Refrigeration | 0 |
| Generators | 0 |
Monthly Overview
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | Total | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Heating | 76244.44 | 60044.72 | 48715.28 | 25382.67 | 10101.0 | 3249.08 | 1300.71 | 2368.38 | 6607.11 | 20400.0 | 36468.06 | 64835.28 | 355716.73 |
| Cooling | 13.57 | 21.6 | 89.16 | 292.31 | 2153.73 | 5803.28 | 9686.25 | 7004.58 | 3028.25 | 418.46 | 48.85 | 13.91 | 28573.95 |
| Interior Lighting | 9274.53 | 8378.94 | 9308.33 | 8924.72 | 9308.33 | 8998.53 | 9234.53 | 9308.33 | 8958.56 | 9274.53 | 8998.53 | 9234.53 | 109202.39 |
| Exterior Lighting | |||||||||||||
| Interior Equipment | 2324.35 | 2099.92 | 2335.12 | 2232.89 | 2335.12 | 2256.72 | 2311.29 | 2335.12 | 2243.66 | 2324.35 | 2256.72 | 2311.29 | 27366.55 |
| Exterior Equipment | |||||||||||||
| Fans | 3628.97 | 3279.75 | 3653.72 | 3591.94 | 4105.78 | 4568.81 | 5232.11 | 4848.14 | 4191.36 | 3756.47 | 3524.94 | 3625.92 | 48007.92 |
| Pumps | 23.13 | 19.34 | 20.18 | 45.19 | 109.27 | 132.58 | 139.54 | 139.14 | 118.31 | 61.18 | 22.89 | 22.41 | 853.15 |
| Heat Rejection | 0.11 | 2.4 | 12.95 | 21.38 | 15.74 | 6.34 | 0.28 | 0.02 | 59.22 | ||||
| Humidification | |||||||||||||
| Heat Recovery | |||||||||||||
| Water Systems | 25917.75 | 23877.64 | 26228.81 | 24429.86 | 23928.44 | 21737.14 | 21268.75 | 20786.22 | 20335.28 | 21933.33 | 22595.56 | 24760.44 | 277799.22 |
| Refrigeration | |||||||||||||
| Generators | |||||||||||||
| Total | 117426.75 | 97721.91 | 90350.59 | 64899.7 | 52044.08 | 46759.08 | 49194.57 | 46805.65 | 45488.86 | 58168.6 | 73915.55 | 104803.78 | 847579.12 |
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Heating | 224.7137 | 200.7231 | 162.9502 | 88.6782 | 47.5225 | 37.1137 | 78.1718 | 134.9336 | 203.1026 | |||
| Cooling | 0.2544 | 0.0289 | 31.2218 | 36.9616 | 26.1833 | 0.3078 | 0.0401 | |||||
| Interior Lighting | 17.3704 | 10.2655 | 17.3704 | 17.3704 | 17.3704 | 17.3704 | 17.3704 | 26.9881 | 17.3704 | 17.3704 | 17.3704 | 17.3704 |
| Exterior Lighting | ||||||||||||
| Interior Equipment | 4.5171 | 2.5544 | 4.5171 | 4.5171 | 4.5171 | 4.5171 | 4.5171 | 6.4671 | 4.5171 | 4.5171 | 4.5171 | 4.5171 |
| Exterior Equipment | ||||||||||||
| Fans | 5.0299 | 5.0299 | 5.0299 | 5.0299 | 5.0299 | 9.624 | 9.8882 | 9.0715 | 5.1381 | 5.0299 | 5.0299 | 5.0299 |
| Pumps | 0.0187 | 0.2573 | 0.0187 | 0.0187 | 0.0187 | 0.2573 | 0.2573 | 0.2573 | 0.0187 | 0.0187 | 0.0187 | 0.0187 |
| Heat Rejection | 0.115 | 0.1571 | 0.0716 | |||||||||
| Humidification | ||||||||||||
| Heat Recovery | ||||||||||||
| Water Systems | 71.518 | 66.125 | 72.9263 | 68.5895 | 73.7763 | 63.2446 | 57.0728 | 45.6039 | 57.1747 | 55.1818 | 69.478 | 65.6155 |
| Refrigeration | ||||||||||||
| Generators | ||||||||||||
| Total | 323.17 | 285.21 | 262.81 | 184.23 | 148.23 | 126.35 | 126.22 | 114.64 | 121.64 | 160.33 | 231.35 | 295.65 |
Utility Bills/Rates
No Data to Show for Utility Bills/Rates
Envelope
| Construction | Net Area (ft^2) | Surface Count | R Value (ft^2*h*R/Btu) |
|---|---|---|---|
| Customized opaque construction {73b3a595-8a62-4734-8b5c-453c65e6af77} to conductance of 0.183 | 10,800 | 16 | 31.03 |
| Customized opaque construction {77828218-a2ca-4c80-9fa2-9fabcf9394e8} to conductance of 0.247 | 16,258 | 92 | 22.99 |
| Construction | Area (ft^2) | Surface Count | U-Factor (Btu/ft^2*h*R) |
|---|---|---|---|
| Customized Fenestration: cond=0.220 tvis=0.220 tsol=0.232 | 1,983 | 103 | 0.3874 |
| Description | Total (%) | North (%) | East (%) | South (%) | West (%) |
|---|---|---|---|---|---|
| Gross Window-Wall Ratio | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
| Gross Window-Wall Ratio (Conditioned) | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
| Skylight-Roof Ratio | 0.0 |
Space Type Breakdown
| Space Type Name | Floor Area (ft^2) | Standards Building Type | Standards Space Type |
|---|---|---|---|
| Space Function Corr. >= 2.4m wide-sch-F | 5,670 | Space Function | Corr. >= 2.4m wide-sch-F |
| Space Function Electrical/Mechanical-sch-F | 1,215 | Space Function | Electrical/Mechanical-sch-F |
| Space Function Gym - fitness | 351 | Space Function | Gym - fitness |
| Space Function Hotel/Motel - lobby | 1,755 | Space Function | Hotel/Motel - lobby |
| Space Function Hway lodging - rooms | 27,271 | Space Function | Hway lodging - rooms |
| Space Function Lobby - elevator | 648 | Space Function | Lobby - elevator |
| Space Function Lounge/recreation | 351 | Space Function | Lounge/recreation |
| Space Function Office - enclosed | 1,404 | Space Function | Office - enclosed |
| Space Function Stairway-sch-F | 1,728 | Space Function | Stairway-sch-F |
| Space Function Storage area - occsens | 2,457 | Space Function | Storage area - occsens |
| Space Function Washroom-sch-F | 351 | Space Function | Washroom-sch-F |
Space Type Summary
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Corr. >= 2.4m wide-sch-F People Definition | 0.0009 | people/ft^2 | 1.0 |
| Space Function Corr. >= 2.4m wide-sch-F Lights Definition | 0.6596 | W/ft^2 | 1.0 |
| Space Function Corr. >= 2.4m wide-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Electrical/Mechanical-sch-F People Definition | 0.0005 | people/ft^2 | 1.0 |
| Space Function Electrical/Mechanical-sch-F Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Electrical/Mechanical-sch-F Lights Definition | 1.2356 | W/ft^2 | 1.0 |
| Space Function Electrical/Mechanical-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Gym - fitness People Definition | 0.0186 | people/ft^2 | 1.0 |
| Space Function Gym - fitness Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Gym - fitness Lights Definition | 0.9104 | W/ft^2 | 1.0 |
| Space Function Gym - fitness Ventilation (outdoor air method Sum) | 0.8600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Hotel/Motel - lobby People Definition | 0.0093 | people/ft^2 | 1.0 |
| Space Function Hotel/Motel - lobby Elec Equip Definition | 0.2323 | W/ft^2 | 1.0 |
| Space Function Hotel/Motel - lobby Lights Definition | 1.0591 | W/ft^2 | 1.0 |
| Space Function Hotel/Motel - lobby Ventilation (outdoor air method Sum) | 0.2850 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Hway lodging - rooms People Definition | 0.0037 | people/ft^2 | 1.0 |
| Space Function Hway lodging - rooms Elec Equip Definition | 0.2323 | W/ft^2 | 1.0 |
| Space Function Hway lodging - rooms Lights Definition | 0.7525 | W/ft^2 | 1.0 |
| Space Function Hway lodging - rooms Ventilation (outdoor air method Sum) | 0.1100 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Lobby - elevator People Definition | 0.0093 | people/ft^2 | 1.0 |
| Space Function Lobby - elevator Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Lobby - elevator Lights Definition | 0.6410 | W/ft^2 | 1.0 |
| Space Function Lobby - elevator Ventilation (outdoor air method Sum) | 0.8100 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Lounge/recreation People Definition | 0.0093 | people/ft^2 | 1.0 |
| Space Function Lounge/recreation Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Lounge/recreation Lights Definition | 0.7860 | W/ft^2 | 1.0 |
| Space Function Lounge/recreation Ventilation (outdoor air method Sum) | 0.1850 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Office - enclosed People Definition | 0.0046 | people/ft^2 | 1.0 |
| Space Function Office - enclosed Elec Equip Definition | 0.6968 | W/ft^2 | 1.0 |
| Space Function Office - enclosed Lights Definition | 1.1055 | W/ft^2 | 1.0 |
| Space Function Office - enclosed Ventilation (outdoor air method Sum) | 0.0850 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Stairway-sch-F People Definition | 0.0005 | people/ft^2 | 1.0 |
| Space Function Stairway-sch-F Lights Definition | 0.6875 | W/ft^2 | 1.0 |
| Space Function Stairway-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Storage area - occsens People Definition | 0.0009 | people/ft^2 | 1.0 |
| Space Function Storage area - occsens Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Storage area - occsens Lights Definition | 0.5686 | W/ft^2 | 1.0 |
| Space Function Storage area - occsens Ventilation (outdoor air method Sum) | 0.0700 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Washroom-sch-F People Definition | 0.0031 | people/ft^2 | 1.0 |
| Space Function Washroom-sch-F Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Washroom-sch-F Lights Definition | 0.8779 | W/ft^2 | 1.0 |
| Space Function Washroom-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
Interior Lighting Summary
| Zone | Lighting Power Density (W/ft^2) | Total Power (W) | Schedule Name | Scheduled Hours/Week (hr) | Actual Load Hours/Week (hr) | Return Air Fraction | Annual Consumption (kWh) | |
|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.66 | 1068.58 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3180.56 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.66 | 890.48 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2650.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.66 | 890.48 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2650.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.66 | 890.48 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2650.0 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION ELECTRICAL/MECHANICAL-SCH-F LIGHTS | SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 1.24 | 433.73 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 1291.67 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION ELECTRICAL/MECHANICAL-SCH-F LIGHTS | SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 1.24 | 1067.63 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3177.78 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN SPACE FUNCTION GYM - FITNESS LIGHTS | SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 0.91 | 319.57 | NECB-B-LIGHTING | 103.58 | 103.57 | 0.0000 | 1725.0 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN SPACE FUNCTION HOTEL/MOTEL - LOBBY LIGHTS | SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 1.06 | 1858.83 | NECB-H-LIGHTING | 151.2 | 151.2 | 0.0000 | 14655.56 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 853.41 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2541.67 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 853.41 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2541.67 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 853.41 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2541.67 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN SPACE FUNCTION LOUNGE/RECREATION LIGHTS | SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 0.79 | 275.87 | NECB-B-LIGHTING | 103.58 | 103.57 | 0.0000 | 1488.89 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN SPACE FUNCTION OFFICE - ENCLOSED LIGHTS | SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 1.11 | 1552.17 | NECB-A-LIGHTING | 56.27 | 56.27 | 0.0000 | 4552.78 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.57 | 598.7 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 1711.11 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION WASHROOM-SCH-F LIGHTS | SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.88 | 308.17 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 916.67 |
Plug Loads Summary
| Electricity Annual Value (kWh) | |
|---|---|
| InteriorEquipment:Electricity:Zone:SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 97.22 |
| InteriorEquipment:Electricity:Zone:SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 238.89 |
| InteriorEquipment:Electricity:Zone:SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 175.0 |
| InteriorEquipment:Electricity:Zone:SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 3213.89 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 783.33 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 783.33 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 783.33 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 175.0 |
| InteriorEquipment:Electricity:Zone:SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 3622.22 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 280.56 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 97.22 |
Exterior Lighting
No Data to Show for Exterior Lighting
Water Use Equipment
| Instance | Plant Loop | Definition | Space | Peak Flow Rate (gal/min) | Flow Rate Schedule | Target Temp Range (F) |
|---|---|---|---|---|---|---|
| Employeeloungeflr1 Service Water Use 0.02gal/min | Main Service Water Loop | Employeeloungeflr1 Service Water Use Def 0.02gal/min | EmployeeLoungeFlr1 | 0.02 | NECB-B-Service Water Heating | 140.0 to 140.0 |
| Exercisecenterflr1 Service Water Use 0.05gal/min | Main Service Water Loop | Exercisecenterflr1 Service Water Use Def 0.05gal/min | ExerciseCenterFlr1 | 0.05 | NECB-B-Service Water Heating | 140.0 to 140.0 |
| Frontloungeflr1 Service Water Use 0.04gal/min | Main Service Water Loop | Frontloungeflr1 Service Water Use Def 0.04gal/min | FrontLoungeFlr1 | 0.04 | NECB-H-Service Water Heating | 140.0 to 140.0 |
| Frontofficeflr1 Service Water Use 0.05gal/min | Main Service Water Loop | Frontofficeflr1 Service Water Use Def 0.05gal/min | FrontOfficeFlr1 | 0.05 | NECB-A-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr1 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr1 Service Water Use Def 0.0gal/min | FrontStorageFlr1 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr2 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr2 Service Water Use Def 0.0gal/min | FrontStorageFlr2 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr3 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr3 Service Water Use Def 0.0gal/min | FrontStorageFlr3 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr4 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr4 Service Water Use Def 0.0gal/min | FrontStorageFlr4 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Guestroom101 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom101 Service Water Use Def 0.07gal/min | GuestRoom101 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom102 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom102 Service Water Use Def 0.07gal/min | GuestRoom102 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom103 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom103 Service Water Use Def 0.07gal/min | GuestRoom103 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom104 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom104 Service Water Use Def 0.07gal/min | GuestRoom104 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom105 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom105 Service Water Use Def 0.07gal/min | GuestRoom105 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom201 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom201 Service Water Use Def 0.07gal/min | GuestRoom201 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom202_205 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom202_205 Service Water Use Def 0.27gal/min | GuestRoom202_205 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom206_208 Service Water Use 0.22gal/min | Main Service Water Loop | Guestroom206_208 Service Water Use Def 0.22gal/min | GuestRoom206_208 | 0.22 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom209_212 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom209_212 Service Water Use Def 0.27gal/min | GuestRoom209_212 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom213 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom213 Service Water Use Def 0.07gal/min | GuestRoom213 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom214 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom214 Service Water Use Def 0.07gal/min | GuestRoom214 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom215_218 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom215_218 Service Water Use Def 0.27gal/min | GuestRoom215_218 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom219 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom219 Service Water Use Def 0.07gal/min | GuestRoom219 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom220_223 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom220_223 Service Water Use Def 0.27gal/min | GuestRoom220_223 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom224 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom224 Service Water Use Def 0.07gal/min | GuestRoom224 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom301 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom301 Service Water Use Def 0.07gal/min | GuestRoom301 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom302_305 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom302_305 Service Water Use Def 0.27gal/min | GuestRoom302_305 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom306_308 Service Water Use 0.22gal/min | Main Service Water Loop | Guestroom306_308 Service Water Use Def 0.22gal/min | GuestRoom306_308 | 0.22 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom309_312 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom309_312 Service Water Use Def 0.27gal/min | GuestRoom309_312 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom313 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom313 Service Water Use Def 0.07gal/min | GuestRoom313 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom314 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom314 Service Water Use Def 0.07gal/min | GuestRoom314 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom315_318 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom315_318 Service Water Use Def 0.27gal/min | GuestRoom315_318 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom319 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom319 Service Water Use Def 0.07gal/min | GuestRoom319 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom320_323 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom320_323 Service Water Use Def 0.27gal/min | GuestRoom320_323 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom324 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom324 Service Water Use Def 0.07gal/min | GuestRoom324 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom401 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom401 Service Water Use Def 0.07gal/min | GuestRoom401 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom402_405 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom402_405 Service Water Use Def 0.27gal/min | GuestRoom402_405 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom406_408 Service Water Use 0.22gal/min | Main Service Water Loop | Guestroom406_408 Service Water Use Def 0.22gal/min | GuestRoom406_408 | 0.22 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom409_412 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom409_412 Service Water Use Def 0.27gal/min | GuestRoom409_412 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom413 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom413 Service Water Use Def 0.07gal/min | GuestRoom413 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom414 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom414 Service Water Use Def 0.07gal/min | GuestRoom414 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom415_418 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom415_418 Service Water Use Def 0.27gal/min | GuestRoom415_418 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom419 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom419 Service Water Use Def 0.07gal/min | GuestRoom419 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom420_423 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom420_423 Service Water Use Def 0.27gal/min | GuestRoom420_423 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom424 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom424 Service Water Use Def 0.07gal/min | GuestRoom424 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Laundryroomflr1 Service Water Use 0.03gal/min | Main Service Water Loop | Laundryroomflr1 Service Water Use Def 0.03gal/min | LaundryRoomFlr1 | 0.03 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr1 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr1 Service Water Use Def 0.01gal/min | RearStorageFlr1 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr2 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr2 Service Water Use Def 0.01gal/min | RearStorageFlr2 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr3 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr3 Service Water Use Def 0.01gal/min | RearStorageFlr3 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr4 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr4 Service Water Use Def 0.01gal/min | RearStorageFlr4 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
HVAC Load Profiles
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Average Outdoor Air Dry Bulb (F) | 14.0 | 16.4 | 27.0 | 41.6 | 56.1 | 64.9 | 70.1 | 67.2 | 58.9 | 46.1 | 34.5 | 19.0 |
| Cooling Load (MBtu) | 0.05 | 0.07 | 0.3 | 1.0 | 7.35 | 19.8 | 33.05 | 23.9 | 10.33 | 1.43 | 0.17 | 0.05 |
| Heating Load (MBtu) | 260.16 | 204.88 | 166.22 | 86.61 | 34.47 | 11.09 | 4.44 | 8.08 | 22.54 | 69.61 | 124.43 | 221.23 |
Zone Conditions
| Zone | Unmet Htg (hr) | Unmet Htg - Occ (hr) | < 56 (F) | 56-61 (F) | 61-66 (F) | 66-68 (F) | 68-70 (F) | 70-72 (F) | 72-74 (F) | 74-76 (F) | 76-78 (F) | 78-83 (F) | 83-88 (F) | >= 88 (F) | Unmet Clg (hr) | Unmet Clg - Occ (hr) | Mean Temp (F) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 92 | 512 | 638 | 3584 | 867 | 3067 | 0 | 0 | 0 | 0 | 0 | 0 | 72.4 (F) |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 265 | 2622 | 1824 | 4044 | 5 | 0 | 0 | 0 | 0 | 0 | 73.3 (F) |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 3 | 366 | 2779 | 1610 | 3998 | 4 | 0 | 0 | 0 | 0 | 0 | 73.2 (F) |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 489 | 401 | 412 | 3446 | 1051 | 2961 | 0 | 0 | 0 | 0 | 0 | 0 | 72.1 (F) |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 2376 | 498 | 591 | 3571 | 577 | 1062 | 66 | 19 | 0 | 0 | 0 | 0 | 69.8 (F) |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 2208 | 739 | 521 | 3582 | 578 | 1047 | 59 | 26 | 0 | 0 | 0 | 0 | 69.9 (F) |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 2221 | 744 | 505 | 3579 | 575 | 1051 | 59 | 26 | 0 | 0 | 0 | 0 | 69.9 (F) |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 2685 | 578 | 306 | 3500 | 496 | 1112 | 60 | 23 | 0 | 0 | 0 | 0 | 69.6 (F) |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 580 | 679 | 442 | 3623 | 911 | 2410 | 105 | 10 | 0 | 0 | 1 | 1 | 71.8 (F) |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 52 | 49 | 0 | 3 | 79 | 198 | 433 | 2324 | 2550 | 2692 | 469 | 12 | 0 | 0 | 0 | 0 | 73.0 (F) |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 51 | 411 | 829 | 4066 | 654 | 2608 | 104 | 37 | 0 | 0 | 78 | 78 | 72.3 (F) |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 69 | 415 | 861 | 1604 | 1803 | 3639 | 368 | 1 | 0 | 0 | 1 | 1 | 72.9 (F) |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 652 | 389 | 412 | 3936 | 769 | 2602 | 0 | 0 | 0 | 0 | 0 | 0 | 71.9 (F) |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 629 | 347 | 431 | 3914 | 740 | 2699 | 0 | 0 | 0 | 0 | 0 | 0 | 72.0 (F) |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 662 | 326 | 433 | 3915 | 718 | 2706 | 0 | 0 | 0 | 0 | 0 | 0 | 71.9 (F) |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 999 | 252 | 333 | 4009 | 623 | 2544 | 0 | 0 | 0 | 0 | 0 | 0 | 71.7 (F) |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 533 | 978 | 1085 | 2229 | 995 | 2403 | 525 | 12 | 0 | 0 | 0 | 0 | 71.8 (F) |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 267 | 1019 | 1128 | 2404 | 879 | 2465 | 574 | 24 | 0 | 0 | 0 | 0 | 72.0 (F) |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 467 | 1019 | 1012 | 2347 | 837 | 2395 | 646 | 37 | 0 | 0 | 0 | 0 | 71.9 (F) |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 1621 | 661 | 727 | 2151 | 826 | 2060 | 566 | 148 | 0 | 0 | 0 | 0 | 71.1 (F) |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 38 | 422 | 2684 | 1745 | 3855 | 16 | 0 | 0 | 0 | 0 | 0 | 73.1 (F) |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 42 | 437 | 2717 | 1704 | 3847 | 13 | 0 | 0 | 0 | 0 | 0 | 73.1 (F) |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 3 | 132 | 591 | 3192 | 1308 | 3531 | 3 | 0 | 0 | 0 | 0 | 0 | 72.8 (F) |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 35 | 327 | 1925 | 2039 | 4427 | 7 | 0 | 0 | 0 | 0 | 0 | 73.4 (F) |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 25 | 280 | 1685 | 2036 | 4703 | 31 | 0 | 0 | 0 | 0 | 0 | 73.5 (F) |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 89 | 263 | 418 | 2991 | 1201 | 3774 | 24 | 0 | 0 | 0 | 0 | 0 | 72.8 (F) |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 10 | 251 | 2081 | 1763 | 4607 | 48 | 0 | 0 | 0 | 4 | 4 | 73.4 (F) |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 27 | 321 | 2355 | 1684 | 4340 | 33 | 0 | 0 | 0 | 0 | 0 | 73.3 (F) |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 18 | 301 | 2307 | 1733 | 4372 | 29 | 0 | 0 | 0 | 0 | 0 | 73.3 (F) |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 1 | 56 | 521 | 2811 | 1476 | 3857 | 38 | 0 | 0 | 0 | 0 | 0 | 73.0 (F) |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 9 | 200 | 1568 | 1920 | 5040 | 23 | 0 | 0 | 0 | 0 | 0 | 73.6 (F) |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 12 | 183 | 1380 | 1827 | 5333 | 25 | 0 | 0 | 0 | 0 | 0 | 73.7 (F) |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 21 | 301 | 1863 | 1985 | 4561 | 29 | 0 | 0 | 0 | 0 | 0 | 73.4 (F) |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 7 | 136 | 1117 | 1748 | 5729 | 23 | 0 | 0 | 0 | 0 | 0 | 73.9 (F) |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 12 | 194 | 1344 | 1922 | 5264 | 24 | 0 | 0 | 0 | 0 | 0 | 73.7 (F) |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 176 | 311 | 436 | 3313 | 999 | 3525 | 0 | 0 | 0 | 0 | 0 | 0 | 72.5 (F) |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 2 | 57 | 370 | 2406 | 1580 | 4312 | 33 | 0 | 0 | 0 | 0 | 0 | 73.2 (F) |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 3 | 82 | 400 | 2482 | 1505 | 4254 | 34 | 0 | 0 | 0 | 0 | 0 | 73.2 (F) |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 3 | 63 | 379 | 2471 | 1560 | 4254 | 30 | 0 | 0 | 0 | 0 | 0 | 73.2 (F) |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 3 | 111 | 561 | 2982 | 1299 | 3772 | 32 | 0 | 0 | 0 | 0 | 0 | 72.9 (F) |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 25 | 282 | 1822 | 1812 | 4795 | 24 | 0 | 0 | 0 | 0 | 0 | 73.5 (F) |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 21 | 224 | 1513 | 1699 | 5275 | 28 | 0 | 0 | 0 | 0 | 0 | 73.7 (F) |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 27 | 317 | 1918 | 1895 | 4577 | 26 | 0 | 0 | 0 | 0 | 0 | 73.4 (F) |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 19 | 207 | 1422 | 1717 | 5367 | 28 | 0 | 0 | 0 | 0 | 0 | 73.7 (F) |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 26 | 284 | 1803 | 1756 | 4866 | 25 | 0 | 0 | 0 | 0 | 0 | 73.5 (F) |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 3 | 3 | 0 | 0 | 711 | 388 | 333 | 3647 | 860 | 2821 | 0 | 0 | 0 | 0 | 0 | 0 | 71.8 (F) |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 4 | 4 | 0 | 0 | 525 | 356 | 375 | 3302 | 991 | 3210 | 1 | 0 | 0 | 0 | 0 | 0 | 72.1 (F) |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 3 | 3 | 0 | 0 | 537 | 357 | 374 | 3296 | 983 | 3212 | 1 | 0 | 0 | 0 | 0 | 0 | 72.1 (F) |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 4 | 4 | 0 | 0 | 526 | 362 | 373 | 3312 | 989 | 3197 | 1 | 0 | 0 | 0 | 0 | 0 | 72.1 (F) |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 569 | 405 | 392 | 3475 | 906 | 3013 | 0 | 0 | 0 | 0 | 0 | 0 | 72.0 (F) |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 441 | 368 | 389 | 2998 | 1150 | 3413 | 1 | 0 | 0 | 0 | 0 | 0 | 72.3 (F) |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 443 | 341 | 368 | 2844 | 1121 | 3631 | 12 | 0 | 0 | 0 | 2 | 2 | 72.4 (F) |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 449 | 395 | 433 | 3066 | 1217 | 3197 | 3 | 0 | 0 | 0 | 0 | 0 | 72.2 (F) |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 440 | 337 | 368 | 2841 | 1115 | 3647 | 12 | 0 | 0 | 0 | 2 | 2 | 72.4 (F) |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 449 | 369 | 382 | 2993 | 1084 | 3480 | 3 | 0 | 0 | 0 | 0 | 0 | 72.3 (F) |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 1289 | 1072 | 681 | 2193 | 1075 | 2021 | 333 | 96 | 0 | 0 | 0 | 0 | 71.1 (F) |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 85 | 537 | 611 | 3666 | 773 | 3085 | 3 | 0 | 0 | 0 | 0 | 0 | 72.4 (F) |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 328 | 560 | 486 | 3708 | 730 | 2940 | 8 | 0 | 0 | 0 | 0 | 0 | 72.2 (F) |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 313 | 394 | 523 | 3971 | 1179 | 2380 | 0 | 0 | 0 | 0 | 0 | 0 | 72.0 (F) |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 270 | 353 | 474 | 3888 | 1108 | 2667 | 0 | 0 | 0 | 0 | 0 | 0 | 72.2 (F) |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 325 | 366 | 485 | 3896 | 1128 | 2560 | 0 | 0 | 0 | 0 | 0 | 0 | 72.1 (F) |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 3 | 3 | 0 | 0 | 838 | 412 | 302 | 4118 | 986 | 2104 | 0 | 0 | 0 | 0 | 0 | 0 | 71.5 (F) |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 1860 | 700 | 583 | 2273 | 781 | 1853 | 564 | 146 | 0 | 0 | 0 | 0 | 70.9 (F) |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 1834 | 678 | 596 | 2249 | 756 | 1879 | 573 | 195 | 0 | 0 | 0 | 0 | 70.9 (F) |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 1929 | 629 | 568 | 2242 | 740 | 1832 | 584 | 236 | 0 | 0 | 0 | 0 | 70.9 (F) |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 2509 | 424 | 432 | 2286 | 652 | 1680 | 474 | 290 | 13 | 0 | 0 | 0 | 70.5 (F) |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 26 | 439 | 658 | 3637 | 721 | 3261 | 18 | 0 | 0 | 0 | 0 | 0 | 72.6 (F) |
| Zone | < 30 (%) | 30-35 (%) | 35-40 (%) | 40-45 (%) | 45-50 (%) | 50-55 (%) | 55-60 (%) | 60-65 (%) | 65-70 (%) | 70-75 (%) | 75-80 (%) | >= 80 (%) | Mean Relative Humidity (%) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 4730 | 728 | 779 | 822 | 702 | 561 | 300 | 118 | 20 | 0 | 0 | 0 | 28.9 (%) |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 4940 | 690 | 648 | 746 | 623 | 501 | 330 | 253 | 29 | 0 | 0 | 0 | 28.7 (%) |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 4920 | 699 | 642 | 753 | 617 | 506 | 335 | 261 | 27 | 0 | 0 | 0 | 28.7 (%) |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 4780 | 701 | 674 | 698 | 611 | 487 | 418 | 232 | 133 | 26 | 0 | 0 | 29.4 (%) |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 4431 | 626 | 555 | 510 | 536 | 571 | 447 | 378 | 301 | 223 | 140 | 42 | 32.8 (%) |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 4451 | 626 | 546 | 502 | 533 | 568 | 439 | 384 | 306 | 225 | 140 | 40 | 32.7 (%) |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 4448 | 628 | 546 | 504 | 533 | 566 | 445 | 381 | 305 | 224 | 140 | 40 | 32.7 (%) |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 4420 | 628 | 551 | 471 | 534 | 557 | 446 | 400 | 323 | 239 | 145 | 46 | 33.0 (%) |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 3794 | 793 | 752 | 688 | 779 | 650 | 563 | 399 | 210 | 87 | 38 | 7 | 35.0 (%) |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 1362 | 674 | 726 | 768 | 850 | 1209 | 1746 | 661 | 522 | 151 | 66 | 25 | 47.0 (%) |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 3688 | 824 | 741 | 636 | 761 | 778 | 618 | 492 | 214 | 8 | 0 | 0 | 35.7 (%) |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 4181 | 796 | 744 | 1403 | 1047 | 560 | 23 | 6 | 0 | 0 | 0 | 0 | 31.1 (%) |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 4773 | 688 | 677 | 703 | 665 | 556 | 362 | 239 | 77 | 20 | 0 | 0 | 29.1 (%) |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 4798 | 707 | 654 | 737 | 666 | 539 | 346 | 234 | 65 | 14 | 0 | 0 | 28.9 (%) |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 4792 | 710 | 663 | 741 | 672 | 543 | 332 | 228 | 70 | 9 | 0 | 0 | 28.9 (%) |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 4735 | 749 | 653 | 741 | 659 | 572 | 301 | 246 | 90 | 14 | 0 | 0 | 29.0 (%) |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 4488 | 786 | 755 | 751 | 714 | 504 | 348 | 186 | 117 | 60 | 30 | 21 | 30.9 (%) |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 4527 | 805 | 703 | 748 | 698 | 501 | 353 | 193 | 119 | 60 | 36 | 17 | 30.8 (%) |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 4522 | 814 | 707 | 740 | 707 | 523 | 335 | 191 | 117 | 55 | 41 | 8 | 30.8 (%) |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 4475 | 812 | 777 | 748 | 641 | 504 | 348 | 235 | 112 | 73 | 27 | 8 | 30.7 (%) |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 1037 | 1098 | 1183 | 1150 | 1081 | 938 | 909 | 645 | 427 | 260 | 32 | 0 | 45.6 (%) |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 1034 | 1094 | 1185 | 1147 | 1073 | 934 | 914 | 654 | 432 | 254 | 39 | 0 | 45.6 (%) |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 993 | 1085 | 1136 | 1103 | 1089 | 963 | 950 | 698 | 457 | 243 | 42 | 1 | 46.0 (%) |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 1109 | 1162 | 1152 | 1188 | 1069 | 903 | 872 | 636 | 400 | 228 | 41 | 0 | 45.1 (%) |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 1162 | 1167 | 1183 | 1199 | 1059 | 912 | 843 | 611 | 383 | 216 | 25 | 0 | 44.7 (%) |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 1919 | 1091 | 1059 | 1129 | 952 | 943 | 760 | 503 | 327 | 76 | 1 | 0 | 41.9 (%) |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1383 | 1225 | 1235 | 1216 | 1026 | 980 | 735 | 526 | 343 | 91 | 0 | 0 | 43.1 (%) |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1358 | 1194 | 1211 | 1193 | 1021 | 927 | 792 | 548 | 349 | 161 | 6 | 0 | 43.6 (%) |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1361 | 1201 | 1202 | 1177 | 1009 | 925 | 773 | 556 | 363 | 187 | 6 | 0 | 43.7 (%) |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1318 | 1161 | 1150 | 1178 | 1069 | 943 | 855 | 566 | 364 | 147 | 9 | 0 | 44.0 (%) |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1463 | 1251 | 1247 | 1142 | 993 | 940 | 727 | 522 | 317 | 152 | 6 | 0 | 43.0 (%) |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1504 | 1267 | 1236 | 1135 | 964 | 905 | 721 | 539 | 334 | 148 | 7 | 0 | 42.9 (%) |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1430 | 1209 | 1164 | 1132 | 994 | 923 | 787 | 574 | 372 | 164 | 11 | 0 | 43.6 (%) |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1567 | 1293 | 1246 | 1142 | 948 | 908 | 682 | 510 | 327 | 136 | 1 | 0 | 42.6 (%) |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1493 | 1278 | 1247 | 1159 | 1019 | 937 | 688 | 512 | 317 | 110 | 0 | 0 | 42.7 (%) |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 1973 | 1041 | 1041 | 1062 | 926 | 903 | 768 | 560 | 337 | 142 | 7 | 0 | 42.2 (%) |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1384 | 1199 | 1207 | 1185 | 1032 | 941 | 765 | 547 | 344 | 153 | 3 | 0 | 43.5 (%) |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1371 | 1198 | 1198 | 1183 | 1044 | 936 | 771 | 545 | 349 | 160 | 5 | 0 | 43.5 (%) |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1377 | 1197 | 1201 | 1174 | 1026 | 917 | 787 | 550 | 353 | 173 | 5 | 0 | 43.6 (%) |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1337 | 1151 | 1152 | 1168 | 1071 | 959 | 854 | 562 | 365 | 132 | 9 | 0 | 43.9 (%) |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1463 | 1257 | 1222 | 1153 | 1004 | 944 | 726 | 526 | 310 | 151 | 4 | 0 | 43.0 (%) |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1531 | 1290 | 1226 | 1144 | 976 | 905 | 710 | 508 | 324 | 144 | 2 | 0 | 42.7 (%) |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1456 | 1225 | 1173 | 1115 | 992 | 921 | 767 | 568 | 366 | 165 | 12 | 0 | 43.5 (%) |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1544 | 1293 | 1230 | 1157 | 970 | 889 | 709 | 501 | 324 | 142 | 1 | 0 | 42.6 (%) |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1465 | 1262 | 1234 | 1173 | 1025 | 936 | 710 | 512 | 314 | 128 | 1 | 0 | 42.9 (%) |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 2472 | 927 | 1015 | 912 | 793 | 875 | 682 | 515 | 350 | 182 | 37 | 0 | 40.8 (%) |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 2186 | 991 | 1044 | 1007 | 842 | 896 | 684 | 510 | 386 | 182 | 32 | 0 | 41.7 (%) |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 2184 | 992 | 1044 | 1008 | 845 | 906 | 677 | 510 | 382 | 182 | 30 | 0 | 41.7 (%) |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 2186 | 991 | 1038 | 1007 | 839 | 897 | 685 | 512 | 387 | 185 | 33 | 0 | 41.8 (%) |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 2172 | 957 | 1026 | 1002 | 874 | 909 | 732 | 547 | 358 | 163 | 20 | 0 | 41.8 (%) |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 2241 | 1021 | 1056 | 977 | 843 | 861 | 690 | 500 | 364 | 174 | 33 | 0 | 41.5 (%) |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 2258 | 1048 | 1054 | 977 | 853 | 836 | 659 | 495 | 370 | 174 | 36 | 0 | 41.3 (%) |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 2240 | 997 | 1029 | 970 | 826 | 847 | 687 | 528 | 391 | 200 | 45 | 0 | 41.7 (%) |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 2258 | 1050 | 1058 | 974 | 852 | 845 | 652 | 495 | 368 | 173 | 35 | 0 | 41.3 (%) |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 2241 | 1021 | 1060 | 986 | 849 | 875 | 680 | 512 | 342 | 174 | 20 | 0 | 41.4 (%) |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 4328 | 803 | 805 | 655 | 709 | 529 | 385 | 271 | 134 | 93 | 41 | 7 | 31.8 (%) |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 4861 | 692 | 721 | 751 | 680 | 520 | 317 | 189 | 29 | 0 | 0 | 0 | 28.5 (%) |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 4817 | 685 | 724 | 792 | 663 | 533 | 335 | 186 | 25 | 0 | 0 | 0 | 28.7 (%) |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 4825 | 664 | 606 | 619 | 612 | 515 | 421 | 269 | 165 | 57 | 7 | 0 | 29.5 (%) |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 4863 | 691 | 580 | 670 | 587 | 499 | 417 | 264 | 153 | 33 | 3 | 0 | 29.2 (%) |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 4853 | 689 | 578 | 671 | 586 | 507 | 419 | 263 | 158 | 32 | 4 | 0 | 29.2 (%) |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 4740 | 699 | 603 | 606 | 617 | 501 | 460 | 251 | 186 | 82 | 15 | 0 | 29.8 (%) |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 4390 | 794 | 779 | 703 | 706 | 513 | 389 | 253 | 126 | 86 | 21 | 0 | 31.2 (%) |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 4406 | 817 | 758 | 731 | 697 | 503 | 391 | 236 | 121 | 90 | 10 | 0 | 31.0 (%) |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 4394 | 830 | 767 | 733 | 705 | 506 | 383 | 228 | 124 | 81 | 9 | 0 | 30.9 (%) |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 4352 | 801 | 780 | 745 | 734 | 472 | 414 | 236 | 146 | 72 | 8 | 0 | 31.0 (%) |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 4187 | 785 | 722 | 841 | 880 | 686 | 462 | 175 | 22 | 0 | 0 | 0 | 32.1 (%) |
Zone Overview
| Area (ft^2) | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume (ft^3) | Multiplier | Above Ground Gross Wall Area (ft^2) | Underground Gross Wall Area (ft^2) | Window Glass Area (ft^2) | Lighting (W/ft^2) | People (ft^2/person) | Plug and Process (W/ft^2) | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 1620.08 | Yes | Yes | 17820.49 | 1.00 | 351.98 | 0.0 | 105.7 | 0.66 | 1075.31 | 0.0 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1350.01 | Yes | Yes | 12150.01 | 1.00 | 197.95 | 0.0 | 28.2 | 0.66 | 1075.31 | 0.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1350.01 | Yes | Yes | 12150.01 | 1.00 | 197.95 | 0.0 | 28.2 | 0.66 | 1075.31 | 0.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1350.01 | Yes | Yes | 12150.01 | 1.00 | 197.95 | 0.0 | 28.2 | 0.66 | 1075.31 | 0.0 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1781.98 | 1.00 | 65.98 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1458.14 | 1.00 | 54.03 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1458.14 | 1.00 | 54.03 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1458.14 | 1.00 | 54.03 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.79 | 107.64 | 0.09 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.91 | 53.82 | 0.09 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 1755.16 | Yes | Yes | 19306.53 | 1.00 | 1012.02 | 0.0 | 159.63 | 1.06 | 107.64 | 0.23 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 15444.16 | 1.00 | 571.99 | 0.0 | 70.83 | 1.11 | 215.06 | 0.7 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 2375.97 | 1.00 | 385.03 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 1944.07 | 1.00 | 314.95 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 1944.07 | 1.00 | 314.95 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 1944.07 | 1.00 | 314.95 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1484.98 | 1.00 | 55.0 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1214.82 | 1.00 | 44.99 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1214.82 | 1.00 | 44.99 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1214.82 | 1.00 | 44.99 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 360.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1134.09 | Yes | Yes | 10206.64 | 1.00 | 378.03 | 0.0 | 72.12 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 360.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1134.09 | Yes | Yes | 10206.64 | 1.00 | 378.03 | 0.0 | 72.12 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 360.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 1134.09 | Yes | Yes | 10206.64 | 1.00 | 378.03 | 0.0 | 72.12 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 1053.03 | Yes | Yes | 11582.86 | 1.00 | 429.05 | 0.0 | 53.17 | 0.57 | 1075.31 | 0.09 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 0.0 | 1.24 | 2173.88 | 0.09 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 864.02 | Yes | Yes | 9504.59 | 1.00 | 351.98 | 0.0 | 53.17 | 1.24 | 2173.88 | 0.09 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 2376.68 | 1.00 | 385.03 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.43 | 1.00 | 315.06 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.43 | 1.00 | 315.06 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.43 | 1.00 | 315.06 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 2376.68 | 1.00 | 385.03 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.78 | 1.00 | 315.06 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.78 | 1.00 | 315.06 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.78 | 1.00 | 315.06 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 0.0 | 0.88 | 322.59 | 0.09 |
| Total | 43201.82 | 410417.54 | 18240.31 | 0.0 | 1982.71 | 0.77 | 287.83 | 0.19 | |||
| Conditioned Total | 43201.82 | 410417.54 | 18240.31 | 0.0 | 1982.71 | 0.77 | 287.83 | 0.19 | |||
| Unconditioned Total | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | |||
| Not Part of Total | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| Heating/Cooling | Calculated Design Load | Design Load With Sizing Factor | Calculated Design Air Flow (ft^3/min) | Design Air Flow With Sizing Factor (ft^3/min) | Date/Time Of Peak | Outdoor Temperature at Peak Load (F) | Outdoor Humidity Ratio at Peak Load (lbWater/lbAir) | |
|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.41 (ton) | 0.45 (ton) | 224.6 | 247.91 | 7/21 16:15:00 | 84.7 | 0.01 |
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 8.73 (kBtu/h) | 11.34 (kBtu/h) | 205.53 | 269.1 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.31 (ton) | 0.34 (ton) | 169.51 | 186.46 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 4.91 (kBtu/h) | 6.38 (kBtu/h) | 116.54 | 150.44 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.32 (ton) | 0.35 (ton) | 175.87 | 192.82 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 6.21 (kBtu/h) | 8.07 (kBtu/h) | 146.2 | 190.7 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.54 (ton) | 0.59 (ton) | 296.64 | 326.31 | 7/21 14:45:00 | 86.18 | 0.01 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 15.44 (kBtu/h) | 20.07 (kBtu/h) | 368.69 | 478.87 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.06 (ton) | 0.07 (ton) | 33.9 | 131.37 | 7/21 17:00:00 | 83.59 | 0.01 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | Heating | 1.13 (kBtu/h) | 1.47 (kBtu/h) | 27.55 | 131.37 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.06 (ton) | 0.06 (ton) | 31.78 | 131.37 | 7/21 17:00:00 | 83.59 | 0.01 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | Heating | 0.76 (kBtu/h) | 0.99 (kBtu/h) | 16.95 | 131.37 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.06 (ton) | 0.07 (ton) | 33.9 | 131.37 | 7/21 17:00:00 | 83.59 | 0.01 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | Heating | 0.89 (kBtu/h) | 1.16 (kBtu/h) | 21.19 | 131.37 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 48.73 | 131.37 | 7/21 14:00:00 | 86.18 | 0.01 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | Heating | 2.11 (kBtu/h) | 2.74 (kBtu/h) | 50.85 | 131.37 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | Cooling | 0.17 (ton) | 0.18 (ton) | 93.23 | 101.71 | 7/21 13:00:00 | 85.26 | 0.01 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | Heating | 1.53 (kBtu/h) | 1.99 (kBtu/h) | 36.02 | 65.69 | 1/21 10:00:00 | -11.74 | 0.0 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | Cooling | 0.23 (ton) | 0.25 (ton) | 125.01 | 300.88 | 7/21 13:00:00 | 85.26 | 0.01 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | Heating | 1.17 (kBtu/h) | 1.53 (kBtu/h) | 27.55 | 300.88 | 1/21 10:00:00 | -11.74 | 0.0 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | Cooling | 0.86 (ton) | 0.95 (ton) | 474.63 | 523.36 | 7/21 14:45:00 | 86.18 | 0.01 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | Heating | 1.2 (kBtu/h) | 1.56 (kBtu/h) | 29.66 | 500.06 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | Cooling | 0.72 (ton) | 0.8 (ton) | 400.47 | 440.73 | 7/21 12:00:00 | 83.77 | 0.01 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | Heating | 6.26 (kBtu/h) | 8.13 (kBtu/h) | 148.32 | 190.7 | 1/21 08:00:00 | -11.74 | 0.0 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | Cooling | 0.04 (ton) | 0.05 (ton) | 23.31 | 25.43 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | Heating | 2.96 (kBtu/h) | 3.85 (kBtu/h) | 69.92 | 91.11 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | Cooling | 0.05 (ton) | 0.05 (ton) | 25.43 | 27.55 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | Heating | 2.57 (kBtu/h) | 3.34 (kBtu/h) | 61.45 | 80.52 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | Cooling | 0.05 (ton) | 0.05 (ton) | 27.55 | 29.66 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | Heating | 2.79 (kBtu/h) | 3.63 (kBtu/h) | 67.8 | 86.87 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 44.5 | 48.73 | 7/21 14:30:00 | 86.18 | 0.01 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | Heating | 4.01 (kBtu/h) | 5.21 (kBtu/h) | 95.35 | 125.01 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.04 (ton) | 0.05 (ton) | 23.31 | 25.43 | 7/21 14:00:00 | 86.18 | 0.01 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Heating | 1.19 (kBtu/h) | 1.55 (kBtu/h) | 27.55 | 36.02 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.03 (ton) | 0.04 (ton) | 19.07 | 21.19 | 7/21 14:00:00 | 86.18 | 0.01 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | Heating | 0.95 (kBtu/h) | 1.24 (kBtu/h) | 23.31 | 29.66 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.04 (ton) | 0.04 (ton) | 19.07 | 21.19 | 7/21 16:00:00 | 85.06 | 0.01 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | Heating | 1.13 (kBtu/h) | 1.47 (kBtu/h) | 27.55 | 36.02 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.06 (ton) | 0.07 (ton) | 33.9 | 38.14 | 7/21 14:00:00 | 86.18 | 0.01 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | Heating | 2.07 (kBtu/h) | 2.69 (kBtu/h) | 48.73 | 63.57 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 46.62 | 50.85 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 1.61 (kBtu/h) | 2.1 (kBtu/h) | 38.14 | 48.73 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 46.62 | 50.85 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 1.74 (kBtu/h) | 2.26 (kBtu/h) | 40.26 | 52.97 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 46.62 | 50.85 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 2.05 (kBtu/h) | 2.67 (kBtu/h) | 48.73 | 63.57 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 48.73 | 52.97 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Heating | 1.96 (kBtu/h) | 2.54 (kBtu/h) | 46.62 | 59.33 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 50.85 | 57.21 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Heating | 1.85 (kBtu/h) | 2.4 (kBtu/h) | 44.5 | 57.21 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | Cooling | 0.12 (ton) | 0.13 (ton) | 65.69 | 72.04 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | Heating | 2.74 (kBtu/h) | 3.56 (kBtu/h) | 65.69 | 84.76 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.4 (ton) | 0.44 (ton) | 220.36 | 241.55 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 4.61 (kBtu/h) | 5.99 (kBtu/h) | 108.06 | 154.68 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.29 (ton) | 0.32 (ton) | 161.03 | 175.87 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 4.18 (kBtu/h) | 5.43 (kBtu/h) | 97.47 | 127.13 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.34 (ton) | 0.38 (ton) | 188.58 | 207.65 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 4.84 (kBtu/h) | 6.3 (kBtu/h) | 114.42 | 154.68 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 50.85 | 57.21 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 1.64 (kBtu/h) | 2.13 (kBtu/h) | 38.14 | 50.85 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.1 (ton) | 0.11 (ton) | 55.09 | 59.33 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 1.55 (kBtu/h) | 2.02 (kBtu/h) | 36.02 | 48.73 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.38 (ton) | 0.42 (ton) | 209.77 | 230.96 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 4.94 (kBtu/h) | 6.42 (kBtu/h) | 116.54 | 154.68 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.1 (ton) | 0.11 (ton) | 57.21 | 61.45 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 1.45 (kBtu/h) | 1.88 (kBtu/h) | 33.9 | 44.5 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.4 (ton) | 0.44 (ton) | 222.48 | 245.79 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 4.8 (kBtu/h) | 6.23 (kBtu/h) | 112.3 | 154.68 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.11 (ton) | 0.12 (ton) | 59.33 | 65.69 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 1.44 (kBtu/h) | 1.87 (kBtu/h) | 33.9 | 44.5 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | Cooling | 0.11 (ton) | 0.12 (ton) | 61.45 | 67.8 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | Heating | 3.38 (kBtu/h) | 4.39 (kBtu/h) | 80.52 | 103.83 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.38 (ton) | 0.42 (ton) | 209.77 | 230.96 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 5.98 (kBtu/h) | 7.78 (kBtu/h) | 141.96 | 184.34 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.31 (ton) | 0.34 (ton) | 169.51 | 186.46 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 5.21 (kBtu/h) | 6.78 (kBtu/h) | 122.9 | 161.03 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.37 (ton) | 0.4 (ton) | 203.41 | 222.48 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 5.96 (kBtu/h) | 7.75 (kBtu/h) | 141.96 | 184.34 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.1 (ton) | 0.11 (ton) | 55.09 | 59.33 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 2.01 (kBtu/h) | 2.61 (kBtu/h) | 46.62 | 61.45 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.1 (ton) | 0.11 (ton) | 57.21 | 63.57 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 1.87 (kBtu/h) | 2.43 (kBtu/h) | 44.5 | 57.21 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.4 (ton) | 0.44 (ton) | 220.36 | 243.67 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 5.96 (kBtu/h) | 7.75 (kBtu/h) | 139.85 | 182.22 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.1 (ton) | 0.11 (ton) | 57.21 | 63.57 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 1.67 (kBtu/h) | 2.17 (kBtu/h) | 40.26 | 50.85 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.4 (ton) | 0.44 (ton) | 222.48 | 243.67 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 5.84 (kBtu/h) | 7.59 (kBtu/h) | 137.73 | 180.1 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.1 (ton) | 0.12 (ton) | 57.21 | 63.57 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 1.74 (kBtu/h) | 2.27 (kBtu/h) | 42.38 | 52.97 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | Cooling | 0.15 (ton) | 0.17 (ton) | 82.64 | 91.11 | 7/21 14:15:00 | 86.18 | 0.01 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | Heating | 5.26 (kBtu/h) | 6.84 (kBtu/h) | 125.01 | 163.15 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.48 (ton) | 0.53 (ton) | 266.98 | 294.52 | 7/21 12:15:00 | 84.15 | 0.01 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 13.12 (kBtu/h) | 17.06 (kBtu/h) | 313.59 | 406.82 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.41 (ton) | 0.45 (ton) | 226.72 | 250.03 | 7/21 12:15:00 | 84.15 | 0.01 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 11.0 (kBtu/h) | 14.3 (kBtu/h) | 262.74 | 341.14 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.48 (ton) | 0.53 (ton) | 264.86 | 292.41 | 7/21 12:15:00 | 84.15 | 0.01 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 13.06 (kBtu/h) | 16.98 (kBtu/h) | 311.48 | 404.71 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.13 (ton) | 0.14 (ton) | 69.92 | 76.28 | 7/21 14:00:00 | 86.18 | 0.01 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 3.97 (kBtu/h) | 5.17 (kBtu/h) | 95.35 | 122.9 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.16 (ton) | 0.18 (ton) | 88.99 | 97.47 | 7/21 12:45:00 | 84.88 | 0.01 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 3.91 (kBtu/h) | 5.09 (kBtu/h) | 93.23 | 120.78 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.63 (ton) | 0.69 (ton) | 345.38 | 381.4 | 7/21 12:30:00 | 84.51 | 0.01 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 13.03 (kBtu/h) | 16.93 (kBtu/h) | 311.48 | 404.71 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.16 (ton) | 0.18 (ton) | 88.99 | 99.59 | 7/21 12:45:00 | 84.88 | 0.01 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 3.79 (kBtu/h) | 4.93 (kBtu/h) | 91.11 | 118.66 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.62 (ton) | 0.68 (ton) | 343.26 | 377.16 | 7/21 12:30:00 | 84.51 | 0.01 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 12.97 (kBtu/h) | 16.86 (kBtu/h) | 309.36 | 402.59 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.16 (ton) | 0.18 (ton) | 88.99 | 97.47 | 7/21 12:45:00 | 84.88 | 0.01 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 3.83 (kBtu/h) | 4.98 (kBtu/h) | 91.11 | 118.66 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.3 (ton) | 0.33 (ton) | 163.15 | 180.1 | 7/21 13:15:00 | 85.48 | 0.01 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Heating | 6.19 (kBtu/h) | 8.05 (kBtu/h) | 146.2 | 190.7 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.09 (ton) | 48.73 | 52.97 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 1.43 (kBtu/h) | 1.86 (kBtu/h) | 33.9 | 44.5 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.2 (ton) | 0.22 (ton) | 110.18 | 120.78 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 3.89 (kBtu/h) | 5.05 (kBtu/h) | 91.11 | 118.66 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | Cooling | 0.05 (ton) | 0.05 (ton) | 25.43 | 27.55 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | Heating | 2.91 (kBtu/h) | 3.79 (kBtu/h) | 69.92 | 91.11 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | Cooling | 0.05 (ton) | 0.05 (ton) | 27.55 | 29.66 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | Heating | 2.51 (kBtu/h) | 3.27 (kBtu/h) | 59.33 | 78.4 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | Cooling | 0.05 (ton) | 0.06 (ton) | 27.55 | 31.78 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | Heating | 2.74 (kBtu/h) | 3.56 (kBtu/h) | 65.69 | 84.76 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 44.5 | 48.73 | 7/21 14:00:00 | 86.18 | 0.01 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | Heating | 3.99 (kBtu/h) | 5.18 (kBtu/h) | 95.35 | 125.01 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | Cooling | 0.05 (ton) | 0.06 (ton) | 29.66 | 33.9 | 7/21 16:00:00 | 85.06 | 0.01 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | Heating | 3.25 (kBtu/h) | 4.22 (kBtu/h) | 78.4 | 101.71 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | Cooling | 0.06 (ton) | 0.06 (ton) | 31.78 | 36.02 | 7/21 16:00:00 | 85.06 | 0.01 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | Heating | 2.9 (kBtu/h) | 3.77 (kBtu/h) | 69.92 | 91.11 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | Cooling | 0.06 (ton) | 0.07 (ton) | 33.9 | 38.14 | 7/21 16:00:00 | 85.06 | 0.01 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | Heating | 3.14 (kBtu/h) | 4.08 (kBtu/h) | 74.16 | 97.47 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | Cooling | 0.1 (ton) | 0.11 (ton) | 55.09 | 61.45 | 7/21 14:00:00 | 86.18 | 0.01 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | Heating | 4.17 (kBtu/h) | 5.42 (kBtu/h) | 99.59 | 129.25 | 1/21 09:00:00 | -11.74 | 0.0 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 48.73 | 52.97 | 7/21 22:00:00 | 73.58 | 0.01 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 1.16 (kBtu/h) | 1.51 (kBtu/h) | 27.55 | 36.02 | 1/21 09:00:00 | -11.74 | 0.0 |
Zone Equipment Detail
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
Air Loops Detail
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.38 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 68.0 to 68.0 | F | |||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 32,185 | ft^2 | 42 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 42 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Make-up air unit Occ Sch | |||||
| Night Cycle Setting | CycleOnAny | Choice | ||||
| Economizer Setting | DifferentialEnthalpy | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-CorridorFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,620 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr1 Sys-3 Flr-2 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr2 Sys-3 Flr-1 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr3 Sys-3 Flr-4 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr4 Sys-3 Flr-3 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-EmployeeLoungeFlr1 Sys-3 Flr-2 Sch-B HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 351 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontLoungeFlr1 Sys-3 Flr-2 Sch-H HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,755 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr1 Sys-4 Flr-2 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr2 Sys-4 Flr-1 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr3 Sys-4 Flr-4 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr4 Sys-4 Flr-3 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr1 Sys-4 Flr-2 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr2 Sys-4 Flr-1 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr3 Sys-4 Flr-4 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr4 Sys-4 Flr-3 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-LaundryRoomFlr1 Sys-4 Flr-2 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,053 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-MechanicalRoomFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 351 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-MeetingRoomFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 864 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr1 Sys-4 Flr-2 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr2 Sys-4 Flr-1 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr3 Sys-4 Flr-4 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr4 Sys-4 Flr-3 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RestroomFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 351 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:Water | Autosized | gal/min | Plant Loop | Chilled Water Loop | ||
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:VariableVolume | Autosized | cfm | Pressure Rise | 5.85 | inH_{2}O | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 55.4 to 55.4 | F | |||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,755 | ft^2 | 2 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:VAV:Reheat | 2 | ||||
(controls) |
||||||
| HVAC Operation Schedule | VAV with Reheat Occ Sch | |||||
| Night Cycle Setting | CycleOnAny | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
Plant Loops Detail
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:ConstantSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:Chiller:Electric:EIR | 33,710.43 | Btu/h | Reference COP | 4.50 | ||
| OS:Chiller:Electric:EIR (cont) | Chiller Source | Condenser Water Loop | ||||
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 44.6 to 44.6 | F | |||
| OS:Chiller:Electric:EIR | 0.00 | Btu/h | Reference COP | 4.50 | ||
| OS:Chiller:Electric:EIR (cont) | Chiller Source | Condenser Water Loop | ||||
(demand) |
||||||
| OS:Coil:Cooling:Water | Air Loop | VAV with Reheat | ||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 32.0 to 212.0 | F | ||||
| Design Loop Exit Temperature | 44.60 | F | ||||
| Loop Design Temperature Difference | 10.80 | R |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:ConstantSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:CoolingTower:SingleSpeed - Air | Autosized | gal/min | ||||
| OS:CoolingTower:SingleSpeed (cont) - Water | Autosized | cfm | Fan Power at Design Air Flow Rate | 383,732.84 | W | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 84.2 to 84.2 | F | |||
(demand) |
||||||
| OS:Chiller:Electric:EIR | Plant Loop | Chilled Water Loop | ||||
| OS:Chiller:Electric:EIR | Plant Loop | Chilled Water Loop | ||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 32.0 to 212.0 | F | ||||
| Design Loop Exit Temperature | 84.20 | F | ||||
| Loop Design Temperature Difference | 10.80 | R |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:ConstantSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:WaterHeater:Mixed | 300 | gal | Heater Thermal Efficiency | 1.00 | fraction | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 140.0 to 140.0 | F | |||
(demand) |
||||||
| OS:WaterUse:Connections | Water Use Connections 1 | |||||
| OS:WaterUse:Connections | Water Use Connections 2 | |||||
| OS:WaterUse:Connections | Water Use Connections 3 | |||||
| OS:WaterUse:Connections | Water Use Connections 4 | |||||
| OS:WaterUse:Connections | Water Use Connections 5 | |||||
| OS:WaterUse:Connections | Water Use Connections 6 | |||||
| OS:WaterUse:Connections | Water Use Connections 7 | |||||
| OS:WaterUse:Connections | Water Use Connections 8 | |||||
| OS:WaterUse:Connections | Water Use Connections 9 | |||||
| OS:WaterUse:Connections | Water Use Connections 10 | |||||
| OS:WaterUse:Connections | Water Use Connections 11 | |||||
| OS:WaterUse:Connections | Water Use Connections 12 | |||||
| OS:WaterUse:Connections | Water Use Connections 13 | |||||
| OS:WaterUse:Connections | Water Use Connections 14 | |||||
| OS:WaterUse:Connections | Water Use Connections 15 | |||||
| OS:WaterUse:Connections | Water Use Connections 16 | |||||
| OS:WaterUse:Connections | Water Use Connections 17 | |||||
| OS:WaterUse:Connections | Water Use Connections 18 | |||||
| OS:WaterUse:Connections | Water Use Connections 19 | |||||
| OS:WaterUse:Connections | Water Use Connections 20 | |||||
| OS:WaterUse:Connections | Water Use Connections 21 | |||||
| OS:WaterUse:Connections | Water Use Connections 22 | |||||
| OS:WaterUse:Connections | Water Use Connections 23 | |||||
| OS:WaterUse:Connections | Water Use Connections 24 | |||||
| OS:WaterUse:Connections | Water Use Connections 25 | |||||
| OS:WaterUse:Connections | Water Use Connections 26 | |||||
| OS:WaterUse:Connections | Water Use Connections 27 | |||||
| OS:WaterUse:Connections | Water Use Connections 28 | |||||
| OS:WaterUse:Connections | Water Use Connections 29 | |||||
| OS:WaterUse:Connections | Water Use Connections 30 | |||||
| OS:WaterUse:Connections | Water Use Connections 31 | |||||
| OS:WaterUse:Connections | Water Use Connections 32 | |||||
| OS:WaterUse:Connections | Water Use Connections 33 | |||||
| OS:WaterUse:Connections | Water Use Connections 34 | |||||
| OS:WaterUse:Connections | Water Use Connections 35 | |||||
| OS:WaterUse:Connections | Water Use Connections 36 | |||||
| OS:WaterUse:Connections | Water Use Connections 37 | |||||
| OS:WaterUse:Connections | Water Use Connections 38 | |||||
| OS:WaterUse:Connections | Water Use Connections 39 | |||||
| OS:WaterUse:Connections | Water Use Connections 40 | |||||
| OS:WaterUse:Connections | Water Use Connections 41 | |||||
| OS:WaterUse:Connections | Water Use Connections 42 | |||||
| OS:WaterUse:Connections | Water Use Connections 43 | |||||
| OS:WaterUse:Connections | Water Use Connections 44 | |||||
| OS:WaterUse:Connections | Water Use Connections 45 | |||||
| OS:WaterUse:Connections | Water Use Connections 46 | |||||
| OS:WaterUse:Connections | Water Use Connections 47 | |||||
| OS:WaterUse:Connections | Water Use Connections 48 | |||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 50.0 to 140.0 | F | ||||
| Design Loop Exit Temperature | 140.00 | F | ||||
| Loop Design Temperature Difference | 9.00 | R |
Outdoor Air
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume (ft^3) | Avg. Mechanical Ventilation (ach) | Min. Mechanical Ventilation (ach) | Avg. Infiltration (ach) | Min. Infiltration (ach) | Avg. Simple Ventilation (ach) | Min. Simple Ventilation (ach) | |
|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.86 | 1.51 | 17820 | 0.332 | 0.319 | 0.031 | 0.0 | 0.0 | 0.0 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.72 | 1.26 | 12150 | 0.456 | 0.393 | 0.033 | 0.0 | 0.0 | 0.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.72 | 1.26 | 12150 | 0.456 | 0.393 | 0.036 | 0.0 | 0.0 | 0.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.72 | 1.26 | 12150 | 0.426 | 0.388 | 0.301 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1782 | 4.488 | 4.35 | 0.065 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1458 | 5.485 | 5.317 | 0.082 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1458 | 5.485 | 5.317 | 0.09 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1458 | 5.485 | 5.317 | 0.387 | 0.0 | 0.0 | 0.0 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 1.56 | 3.26 | 3861 | 1.027 | 0.988 | 0.061 | 0.0 | 0.0 | 0.0 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 3.12 | 6.52 | 3861 | 1.178 | 0.0 | 0.061 | 0.0 | 0.0 | 0.0 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 14.67 | 16.31 | 19307 | 1.58 | 1.516 | 0.083 | 0.0 | 0.0 | 0.0 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 3.51 | 6.53 | 15444 | 0.709 | 0.0 | 0.063 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 2376 | 0.332 | 0.318 | 0.257 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 1944 | 0.406 | 0.388 | 0.323 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 1944 | 0.406 | 0.388 | 0.357 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 1944 | 0.405 | 0.388 | 0.645 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1485 | 0.388 | 0.375 | 0.067 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1215 | 0.475 | 0.458 | 0.084 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1215 | 0.475 | 0.458 | 0.093 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1215 | 0.475 | 0.46 | 0.4 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3861 | 0.687 | 0.589 | 0.059 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3861 | 0.684 | 0.589 | 0.059 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3861 | 0.671 | 0.588 | 0.059 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3861 | 0.691 | 0.589 | 0.059 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3861 | 0.708 | 0.59 | 0.059 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 0.75 | 1.31 | 3159 | 0.843 | 0.715 | 0.227 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.873 | 0.72 | 0.074 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 2.42 | 4.22 | 10207 | 0.86 | 0.72 | 0.074 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.856 | 0.72 | 0.074 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3159 | 0.853 | 0.719 | 0.074 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.875 | 0.721 | 0.074 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.876 | 0.722 | 0.074 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.856 | 0.721 | 0.074 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.886 | 0.722 | 0.074 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.883 | 0.721 | 0.074 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 0.75 | 1.31 | 3159 | 0.811 | 0.714 | 0.251 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.86 | 0.719 | 0.082 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 2.42 | 4.22 | 10207 | 0.86 | 0.719 | 0.082 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.857 | 0.719 | 0.082 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3159 | 0.85 | 0.719 | 0.082 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.873 | 0.72 | 0.082 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.882 | 0.721 | 0.082 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.857 | 0.72 | 0.082 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.884 | 0.721 | 0.082 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.879 | 0.721 | 0.082 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 0.75 | 1.31 | 3159 | 0.783 | 0.712 | 0.531 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.803 | 0.713 | 0.35 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 2.42 | 4.22 | 10207 | 0.804 | 0.713 | 0.35 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.802 | 0.713 | 0.35 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3159 | 0.794 | 0.713 | 0.35 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.808 | 0.714 | 0.35 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.822 | 0.713 | 0.35 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.806 | 0.713 | 0.35 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.822 | 0.713 | 0.35 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.812 | 0.713 | 0.35 | 0.0 | 0.0 | 0.0 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.62 | 0.98 | 11583 | 0.388 | 0.375 | 0.067 | 0.0 | 0.0 | 0.0 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.09 | 0.16 | 3861 | 0.332 | 0.319 | 0.059 | 0.0 | 0.0 | 0.0 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.23 | 0.4 | 9505 | 0.332 | 0.318 | 0.059 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 2377 | 0.34 | 0.318 | 0.257 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 1944 | 0.417 | 0.389 | 0.323 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 1944 | 0.418 | 0.389 | 0.357 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 1944 | 0.433 | 0.388 | 0.644 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 2377 | 0.388 | 0.376 | 0.294 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 1945 | 0.475 | 0.459 | 0.369 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 1945 | 0.475 | 0.459 | 0.408 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 1945 | 0.474 | 0.46 | 0.738 | 0.0 | 0.0 | 0.0 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.62 | 1.09 | 3861 | 0.333 | 0.32 | 0.059 | 0.0 | 0.0 | 0.0 |
Cash Flow
No Data to Show for Cash Flow
Site and Source Summary
| Total Energy (kBtu) | Energy Per Total Building Area (kBtu/ft^2) | Energy Per Conditioned Building Area (kBtu/ft^2) | |
|---|---|---|---|
| Total Site Energy | 2892064.9 | 66.9 | 66.9 |
| Net Site Energy | 2892064.9 | 66.9 | 66.9 |
| Total Source Energy | 9159154.8 | 212.0 | 212.0 |
| Net Source Energy | 9159154.8 | 212.0 | 212.0 |
| Site=>Source Conversion Factor | |
|---|---|
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
Schedule Overview
| Schedule | Type Limits | Rules | Use Count |
|---|---|---|---|
| Air Velocity Schedule | Velocity | 0 | 11 |
| Always On | Dimensionless | 0 | 67 |
| CHW Temp | Temperature | 3 | 1 |
| Clothing Schedule | ClothingInsulation | 1 | 11 |
| CW Temp | Temperature | 3 | 1 |
| Make-up air unit Occ Sch | Dimensionless | 7 | 2 |
| Makeup-Air Unit Supply Air Temp | Temperature | 0 | 1 |
| NECB-A-Electric-Equipment | Dimensionless | 3 | 1 |
| NECB-A-Lighting | Dimensionless | 3 | 1 |
| NECB-A-Occupancy | Dimensionless | 3 | 1 |
| NECB-A-Service Water Heating | Dimensionless | 3 | 1 |
| NECB-A-Thermostat Setpoint-Cooling | Temperature | 3 | 3 |
| NECB-A-Thermostat Setpoint-Heating | Temperature | 3 | 3 |
| NECB-Activity | ActivityLevel | 0 | 67 |
| NECB-B-Electric-Equipment | Dimensionless | 3 | 2 |
| NECB-B-Lighting | Dimensionless | 3 | 2 |
| NECB-B-Occupancy | Dimensionless | 3 | 2 |
| NECB-B-Service Water Heating | Dimensionless | 3 | 2 |
| NECB-B-Thermostat Setpoint-Cooling | Temperature | 3 | 6 |
| NECB-B-Thermostat Setpoint-Heating | Temperature | 3 | 6 |
| NECB-C-Electric-Equipment | Dimensionless | 3 | 4 |
| NECB-C-Lighting | Dimensionless | 3 | 4 |
| NECB-C-Occupancy | Dimensionless | 3 | 4 |
| NECB-C-Thermostat Setpoint-Cooling | Temperature | 3 | 9 |
| NECB-C-Thermostat Setpoint-Heating | Temperature | 3 | 9 |
| NECB-E-Electric-Equipment | Dimensionless | 3 | 9 |
| NECB-E-Lighting | Dimensionless | 3 | 9 |
| NECB-E-Occupancy | Dimensionless | 3 | 9 |
| NECB-E-Service Water Heating | Dimensionless | 3 | 9 |
| NECB-E-Thermostat Setpoint-Cooling | Temperature | 3 | 19 |
| NECB-E-Thermostat Setpoint-Heating | Temperature | 3 | 19 |
| NECB-F-Electric-Equipment | Dimensionless | 3 | 50 |
| NECB-F-Lighting | Dimensionless | 3 | 50 |
| NECB-F-Occupancy | Dimensionless | 3 | 50 |
| NECB-F-Service Water Heating | Dimensionless | 3 | 35 |
| NECB-F-Thermostat Setpoint-Cooling | Temperature | 3 | 105 |
| NECB-F-Thermostat Setpoint-Heating | Temperature | 3 | 105 |
| NECB-H-Electric-Equipment | Dimensionless | 3 | 1 |
| NECB-H-Lighting | Dimensionless | 3 | 1 |
| NECB-H-Occupancy | Dimensionless | 3 | 1 |
| NECB-H-Service Water Heating | Dimensionless | 3 | 1 |
| NECB-H-Thermostat Setpoint-Cooling | Temperature | 3 | 3 |
| NECB-H-Thermostat Setpoint-Heating | Temperature | 3 | 3 |
| ON_OFF_ALWAYS_OFF | Availability | 3 | 42 |
| Schedule Ruleset 10 | 0 | 1 | |
| Schedule Ruleset 100 | 0 | 1 | |
| Schedule Ruleset 101 | 0 | 1 | |
| Schedule Ruleset 102 | 0 | 1 | |
| Schedule Ruleset 103 | 0 | 1 | |
| Schedule Ruleset 104 | 0 | 1 | |
| Schedule Ruleset 105 | 0 | 1 | |
| Schedule Ruleset 106 | 0 | 1 | |
| Schedule Ruleset 107 | 0 | 1 | |
| Schedule Ruleset 108 | 0 | 1 | |
| Schedule Ruleset 109 | 0 | 1 | |
| Schedule Ruleset 11 | 0 | 1 | |
| Schedule Ruleset 110 | 0 | 1 | |
| Schedule Ruleset 111 | 0 | 1 | |
| Schedule Ruleset 112 | 0 | 1 | |
| Schedule Ruleset 113 | 0 | 1 | |
| Schedule Ruleset 114 | 0 | 1 | |
| Schedule Ruleset 115 | 0 | 1 | |
| Schedule Ruleset 116 | 0 | 1 | |
| Schedule Ruleset 117 | 0 | 1 | |
| Schedule Ruleset 118 | 0 | 1 | |
| Schedule Ruleset 119 | 0 | 1 | |
| Schedule Ruleset 12 | 0 | 1 | |
| Schedule Ruleset 120 | 0 | 1 | |
| Schedule Ruleset 121 | 0 | 1 | |
| Schedule Ruleset 122 | 0 | 1 | |
| Schedule Ruleset 123 | 0 | 1 | |
| Schedule Ruleset 124 | 0 | 1 | |
| Schedule Ruleset 125 | 0 | 1 | |
| Schedule Ruleset 126 | 0 | 1 | |
| Schedule Ruleset 127 | 0 | 1 | |
| Schedule Ruleset 128 | 0 | 1 | |
| Schedule Ruleset 129 | 0 | 1 | |
| Schedule Ruleset 13 | 0 | 1 | |
| Schedule Ruleset 130 | 0 | 1 | |
| Schedule Ruleset 131 | 0 | 1 | |
| Schedule Ruleset 132 | 0 | 1 | |
| Schedule Ruleset 133 | 0 | 1 | |
| Schedule Ruleset 134 | 0 | 1 | |
| Schedule Ruleset 135 | 0 | 1 | |
| Schedule Ruleset 136 | 0 | 1 | |
| Schedule Ruleset 137 | 0 | 1 | |
| Schedule Ruleset 138 | 0 | 1 | |
| Schedule Ruleset 139 | 0 | 1 | |
| Schedule Ruleset 14 | 0 | 1 | |
| Schedule Ruleset 140 | 0 | 1 | |
| Schedule Ruleset 141 | 0 | 1 | |
| Schedule Ruleset 142 | 0 | 1 | |
| Schedule Ruleset 143 | 0 | 1 | |
| Schedule Ruleset 144 | 0 | 1 | |
| Schedule Ruleset 145 | 0 | 1 | |
| Schedule Ruleset 146 | 0 | 1 | |
| Schedule Ruleset 15 | 0 | 1 | |
| Schedule Ruleset 16 | 0 | 1 | |
| Schedule Ruleset 17 | 0 | 1 | |
| Schedule Ruleset 18 | 0 | 1 | |
| Schedule Ruleset 19 | 0 | 1 | |
| Schedule Ruleset 20 | 0 | 1 | |
| Schedule Ruleset 21 | 0 | 1 | |
| Schedule Ruleset 22 | 0 | 1 | |
| Schedule Ruleset 23 | 0 | 1 | |
| Schedule Ruleset 24 | 0 | 1 | |
| Schedule Ruleset 25 | 0 | 1 | |
| Schedule Ruleset 26 | 0 | 1 | |
| Schedule Ruleset 27 | 0 | 1 | |
| Schedule Ruleset 28 | 0 | 1 | |
| Schedule Ruleset 29 | 0 | 1 | |
| Schedule Ruleset 3 | 0 | 1 | |
| Schedule Ruleset 30 | 0 | 1 | |
| Schedule Ruleset 31 | 0 | 1 | |
| Schedule Ruleset 32 | 0 | 1 | |
| Schedule Ruleset 33 | 0 | 1 | |
| Schedule Ruleset 34 | 0 | 1 | |
| Schedule Ruleset 35 | 0 | 1 | |
| Schedule Ruleset 36 | 0 | 1 | |
| Schedule Ruleset 37 | 0 | 1 | |
| Schedule Ruleset 38 | 0 | 1 | |
| Schedule Ruleset 39 | 0 | 1 | |
| Schedule Ruleset 4 | 0 | 1 | |
| Schedule Ruleset 40 | 0 | 1 | |
| Schedule Ruleset 41 | 0 | 1 | |
| Schedule Ruleset 42 | 0 | 1 | |
| Schedule Ruleset 43 | 0 | 1 | |
| Schedule Ruleset 44 | 0 | 1 | |
| Schedule Ruleset 45 | 0 | 1 | |
| Schedule Ruleset 46 | 0 | 1 | |
| Schedule Ruleset 47 | 0 | 1 | |
| Schedule Ruleset 48 | 0 | 1 | |
| Schedule Ruleset 49 | 0 | 1 | |
| Schedule Ruleset 5 | 0 | 1 | |
| Schedule Ruleset 50 | 0 | 1 | |
| Schedule Ruleset 51 | 0 | 1 | |
| Schedule Ruleset 52 | 0 | 1 | |
| Schedule Ruleset 53 | 0 | 1 | |
| Schedule Ruleset 54 | 0 | 1 | |
| Schedule Ruleset 55 | 0 | 1 | |
| Schedule Ruleset 56 | 0 | 1 | |
| Schedule Ruleset 57 | 0 | 1 | |
| Schedule Ruleset 58 | 0 | 1 | |
| Schedule Ruleset 59 | 0 | 1 | |
| Schedule Ruleset 6 | 0 | 1 | |
| Schedule Ruleset 60 | 0 | 1 | |
| Schedule Ruleset 61 | 0 | 1 | |
| Schedule Ruleset 62 | 0 | 1 | |
| Schedule Ruleset 63 | 0 | 1 | |
| Schedule Ruleset 64 | 0 | 1 | |
| Schedule Ruleset 65 | 0 | 1 | |
| Schedule Ruleset 66 | 0 | 1 | |
| Schedule Ruleset 67 | 0 | 1 | |
| Schedule Ruleset 68 | 0 | 1 | |
| Schedule Ruleset 69 | 0 | 1 | |
| Schedule Ruleset 7 | 0 | 1 | |
| Schedule Ruleset 70 | 0 | 1 | |
| Schedule Ruleset 71 | 0 | 1 | |
| Schedule Ruleset 72 | 0 | 1 | |
| Schedule Ruleset 73 | 0 | 1 | |
| Schedule Ruleset 74 | 0 | 1 | |
| Schedule Ruleset 75 | 0 | 1 | |
| Schedule Ruleset 76 | 0 | 1 | |
| Schedule Ruleset 77 | 0 | 1 | |
| Schedule Ruleset 78 | 0 | 1 | |
| Schedule Ruleset 79 | 0 | 1 | |
| Schedule Ruleset 8 | 0 | 1 | |
| Schedule Ruleset 80 | 0 | 1 | |
| Schedule Ruleset 81 | 0 | 1 | |
| Schedule Ruleset 82 | 0 | 1 | |
| Schedule Ruleset 83 | 0 | 1 | |
| Schedule Ruleset 84 | 0 | 1 | |
| Schedule Ruleset 85 | 0 | 1 | |
| Schedule Ruleset 86 | 0 | 1 | |
| Schedule Ruleset 87 | 0 | 1 | |
| Schedule Ruleset 88 | 0 | 1 | |
| Schedule Ruleset 89 | 0 | 1 | |
| Schedule Ruleset 9 | 0 | 1 | |
| Schedule Ruleset 90 | 0 | 1 | |
| Schedule Ruleset 91 | 0 | 1 | |
| Schedule Ruleset 92 | 0 | 1 | |
| Schedule Ruleset 93 | 0 | 1 | |
| Schedule Ruleset 94 | 0 | 1 | |
| Schedule Ruleset 95 | 0 | 1 | |
| Schedule Ruleset 96 | 0 | 1 | |
| Schedule Ruleset 97 | 0 | 1 | |
| Schedule Ruleset 98 | 0 | 1 | |
| Schedule Ruleset 99 | 0 | 1 | |
| Service Water Loop Temp - 140F | Temperature | 0 | 2 |
| Supply Air Temp | Temperature | 0 | 1 |
| VAV with Reheat Occ Sch | Dimensionless | 7 | 2 |
| Water Heater Ambient Temp Schedule - 70F | Temperature | 0 | 1 |
| Work Efficiency Schedule | Dimensionless | 0 | 11 |